Load Calculation

Compute connected and demand loads for dwelling units, multifamily buildings, commercial occupancies, and feeders per NEC 2026.

Calculation Method

1
Building / System Information

220.12, 220.14

Gross Floor Area120.5(C)
ft²
Voltage System220.5(A)
2
Small Appliance & Laundry Circuits

220.52

Minimum 2 small-appliance circuits at 1,500 VA each (220.52(A)) and 1 laundry circuit at 1,500 VA (220.52(B)).

Small Appliance Circuits220.52(A)
Laundry Circuits220.52(B)
Combined with general lighting and subject to Table 220.42 demand factors.
3
Fixed Appliances

220.53

4
Cooking Equipment (Range / Oven)

220.55 / Table 220.55

Note 4: Single range ≤ 8¾ kW → 8 kW demand.

Note 2: Range > 8¾ kW to ≤ 12 kW → Col C at 12 kW. Unequal ratings > 8¾ kW through 27 kW → average rating (12 kW floor per range) bumps Col C.

Note 1: Ranges all the same rating, > 12 kW → add 5% per kW over 12 kW.

5
Electric Clothes Dryer

220.54 / Table 220.54

Minimum load 5,000 VA per dryer per 220.54. Demand % is based on total dryer count, applied to the summed nameplate total: 1–4 units = 100%; 5 = 85%; 6 = 75%…
6
HVAC — Heating & Cooling

220.60

Add each heating and/or cooling unit's connected load. Noncoincident rule (§220.60) uses the larger of the two totals — both are not added together.

7
EVSE (Electric Vehicle Charging)

120.57

⚡

Results will appear here

Enter the required inputs to the left to compute load.

Disclaimer

The calculators and tools provided on this website ("EEE Corp Calculators") are intended for informational and preliminary design assistance purposes only. Results are based on the National Electrical Code (NEC/NFPA 70) and general industry practices as interpreted at the time of development, and may not reflect the most current code edition, local amendments, or Authority Having Jurisdiction (AHJ) requirements applicable to your project.

These calculators do not account for every possible electrical scenario, edge case, or site condition. Factors such as unusual load profiles, non-standard installation methods, environmental conditions, existing infrastructure limitations, and project-specific constraints may affect the correct design and are not necessarily captured by these tools.

These tools do not constitute professional engineering advice, and their output should not be relied upon as a substitute for review, calculation, and sign-off by a licensed Professional Engineer (P.E.) or qualified electrical professional. Local codes, utility requirements, and site-specific conditions can materially affect the correct design and sizing of electrical systems.

EEE Corp makes no warranty, express or implied, as to the accuracy, completeness, or fitness of these calculations for any particular installation. Use of this tool and its results is at your own risk, and EEE Corp assumes no liability for damages, code violations, permit rejections, or safety issues arising from reliance on calculator output. Always verify results against the applicable code edition and consult a licensed engineer or electrician before construction, installation, or permitting.