← HomePro Electrical Toolkit
Translate to Spanish

How to Use Pro Electrical Toolkit

A plain-language guide to the homepage and every calculator

This guide walks through what each calculator on this site is for, what to type into it, and what the results mean — no electrical background required. Use the list below to jump straight to the section you need.

Homepage Overview

The homepage groups every calculator into three sections: Core Calculators(Voltage Drop, Wire Size, Breaker Size, Ohm's Law, kVA ↔ kW Conversion — free for everyone), Specific Calculators (Load Calculation, Motors, Transformer, HVAC — also free for everyone), and PE Exam Preparation (practice questions for the NCEES PE Power exam). Click any card to open that calculator.

The navigation bar at the top has links to Home, Plan (view or change your subscription), PE Exam Prep, and this How to Use guide — which includes an FAQ section covering both calculator usage and subscription/billing questions. Once signed in, you'll also see a Saved Reports menu (up to 10 saved reports on Free, 30 on Pro, 50 on Premium) and a link to contact support.

Plans & access

Every calculator, including report generation, is free for everyone — no plan or sign-in required. Saving a report just needs a free sign-in. Free includes up to 10 saved reports and limited PE Exam practice (10 questions/day). Pro raises the saved-reports cap to 30 and adds unlimited PE Exam practice with progress tracking. Premiumraises it to 50 and adds timed PE exams with a wrong-answer review. Opening a PE Exam feature your plan doesn't include will redirect you to the Plan page to upgrade.

Voltage Drop CalculatorFree · Pro · Premium

Checks how much electrical “pressure” (voltage) a wire loses by the time power reaches your load, comparing two accepted calculation methods side by side.

How to use it

  1. Choose US/Imperial units (feet, AWG) or Metric (meters, mm²).
  2. Choose Single-phase or Three-phase.
  3. Pick the wire material (Copper or Aluminum), wire size, and Solid or Stranded construction.
  4. Pick the conduit type (Steel or non-metallic) — this only affects one of the two methods.
  5. Enter the run length, the load current, the source voltage, and the power factor (lagging or leading).
  6. Read the two results side by side.

Input fields

  • Distance / run lengthAny positive number, in feet or meters.
  • Load currentAny positive number, in Amps.
  • Source voltageAny positive number, in Volts.
  • Power factorA decimal between 0 and 1 (e.g. 0.85), lagging or leading.
  • Wire material / size / constructionChosen from standard Copper/Aluminum, AWG/kcmil, and Solid/Stranded options.

What the result means

Two voltage-drop percentages side by side, one per method. Under 3% is marked OK (green), 3–5% is a Warning (amber), and over 5% is a Fail (red) because it exceeds the NEC's recommended limit. It also separately warns if your entered current is more than that wire can safely carry.

Common mistakes & things to watch for

  • The Table 9 (AC Impedance) method doesn't have data for every wire size — some sizes, and larger aluminum sizes, simply aren't in the table, and the calculator says so instead of guessing.
  • A result over 5% doesn't mean the circuit is illegal to build — it means it doesn't meet the NEC's recommended voltage-drop guideline, and a larger wire or shorter run would help.
  • Watch the separate ampacity warning — a wire can pass the voltage-drop check and still be too small for the current it's carrying.
Voltage Drop — Other ScenariosFree · Pro · Premium

Open the Voltage Drop Calculator, then click “Other Scenarios →”.

Runs the voltage-drop math backwards — instead of telling you the drop, you tell it the maximum drop you'll accept and it solves for length, current, or wire size.

How to use it

  1. Open it from the Voltage Drop Calculator's “Other Scenarios” link.
  2. Choose the unit system (US/Imperial or Metric).
  3. Pick what to solve for: Voltage Drop, Conductor Length, Load Current, or Conductor Size.
  4. Choose the calculation method (K-Formula or Table 9 AC Impedance).
  5. Enter your target maximum voltage drop % (defaults to 3.6%) and the other known values.
  6. Read the solved result.

Input fields

  • Solve forVoltage Drop, Conductor Length, Load Current, or Conductor Size.
  • Target voltage drop %Defaults to 3.6%, editable.
  • Everything elseSame fields as the main Voltage Drop Calculator — fill in all except the one you're solving for.

What the result means

The solved value, plus a warning if the answer would require a wire larger than the largest standard size, or if your known current already exceeds what that wire size can carry.

Common mistakes & things to watch for

  • If solving for Conductor Size returns a warning instead of a size, your inputs need an unrealistically large conductor — consider parallel conductors or a higher voltage system.
Wire Size CalculatorFree · Pro · Premium

Figures out the minimum wire size for your circuit's ampacity, the ground wire size, or the grounding electrode wire size, across three tabs.

How to use it

  1. Conductor Ampacity tab: enter continuous and non-continuous load current (or add motor loads), the wire material, and the installation condition (raceway, free air, high-temperature insulation, or messenger-supported).
  2. Enter the ambient temperature (°F or °C), how many current-carrying conductors are bundled together, and whether the run is on an exposed rooftop.
  3. Equipment Grounding Conductor tab: enter the breaker/fuse size feeding the circuit and the wire material to look up the required ground wire size.
  4. Grounding Electrode Conductor tab: enter your largest ungrounded (hot) conductor size, its material, and the electrode type to look up the required grounding electrode conductor size.

Input fields

  • Continuous / non-continuous ampsPositive numbers; continuous loads automatically get a 1.25× safety margin.
  • Motor loadsPick horsepower, voltage, and phase from dropdowns — the standard motor current is looked up for you.
  • Material / conditionCopper or Aluminum; Raceway, Free Air, High-Temp Raceway, High-Temp Free Air, or Messenger-Supported.
  • Ambient temperatureA number in °F or °C.
  • Conductor countHow many current-carrying wires share the same raceway — more wires bundled together reduces capacity.
  • EGC tab: OCPD size, material, parallel setsOCPD is the breaker/fuse rating protecting the circuit.
  • GEC tab: ungrounded conductor size, material, parallel sets, electrode type

What the result means

The minimum standard wire size (AWG or kcmil) large enough for your load after all temperature and bundling adjustments — or “out of range” if your ambient temperature is outside what the tables cover.

Common mistakes & things to watch for

  • If the ambient temperature is too high for the insulation you picked, the calculator says no conductor can be used at that location instead of guessing — you'll need higher-temperature-rated insulation.
  • 14 AWG aluminum isn't in the ampacity tables under the 2020/2023 NEC. The 2026 NEC adds it, but only for copper-clad aluminum conductors — the calculator shows a note when this applies.
  • For large loads (over 100 A, or anything with a motor), the calculator automatically switches to the 75°C column instead of 60°C, per code — you don't need to set this yourself.
Ampacity — Other ScenariosFree · Pro · Premium

Open the Wire Size Calculator, then click “Other Scenarios →”.

The reverse of the Wire Size Calculator's Ampacity tab — instead of always solving for wire size, you choose what to solve for.

How to use it

  1. Open it from the Wire Size Calculator's “Other Scenarios” link.
  2. Pick what to solve for: Ampacity (given a conductor), Conductor Size (given a required ampacity), Max Ambient Temperature, or Max Conductor Count.
  3. Fill in the remaining fields — the same inputs as the Wire Size Calculator's Ampacity tab.
  4. Read the solved result.

Input fields

  • EverythingSame fields as the Wire Size Calculator's Ampacity tab, minus whichever one you're solving for.

What the result means

The solved value — e.g. the maximum ambient temperature a given wire can handle, instead of always returning a wire size.

Common mistakes & things to watch for

  • An “Out of Range” result means the temperature or load you asked about is outside what the NEC tables cover, not a bug.
Ohm's Law CalculatorFree · Pro · Premium

Solves Voltage, Current, and Resistance (or Impedance for AC) for you — enter any two of the three, and it calculates the third, for both DC and AC circuits.

How to use it

  1. Pick the DC panel or the AC panel.
  2. Type in any two of the three main values (DC: Voltage, Current, Resistance; AC: Voltage, Current, Impedance).
  3. Leave the value you want solved blank.
  4. For AC, optionally add Resistance, Reactance, or Power Factor for more detail (the power triangle).

Input fields

  • DC: Voltage, Current, ResistanceEnter any two; Resistance can't be negative.
  • AC: Voltage, Current, ImpedanceEnter any two; Impedance can't be negative.
  • Power Factor (optional, AC)Must be between 0 and 1.

What the result means

The missing value, plus — for AC — real power (Watts), reactive power (VAR), apparent power (VA), and the phase angle.

Common mistakes & things to watch for

  • “Enter any two values — the third will be solved.” — shown if fewer than two fields are filled in.
  • “Resistance (R) cannot be negative.” / “Impedance (Z) cannot be negative.”
  • If all three values are filled in and they don't agree with each other (V ≠ I × R), you'll see an “Inconsistent values” message — clear one field and let the calculator solve it instead of overriding your numbers.
  • “R = 0 Ω (short circuit)” or “I = 0 A (open circuit)” messages are mathematically correct results, not bugs — they usually mean a typo in one of your numbers.
  • “Power Factor must be between 0 and 1.”
kVA ↔ kW ConversionFree · Pro · Premium

Converts between apparent power (kVA), real power (kW), and reactive power (kVAR) three different ways, depending on what you already know.

How to use it

  1. Pick a tab: PF-Based, Power Triangle, or Voltage & Current.
  2. PF-Based: enter kVA or kW plus the power factor slider to get the other.
  3. Power Triangle: enter any two of kVA/kW/kVAR (or kW + power factor) to get the third, plus the phase angle.
  4. Voltage & Current: enter voltage, current, and phase to get kVA/kW/kVAR, or voltage + kVA to solve for current.

Input fields

  • Power factorSlider from 0 to 1, defaults to 0.85.
  • kVA / kW / kVARPositive numbers; kW can be exactly 0 but not negative.
  • Voltage / CurrentPositive numbers.
  • PhaseSingle-phase, Three-phase line-to-line, or Three-phase line-to-neutral.

What the result means

The converted kVA, kW, kVAR, and/or current value, with the formula used shown for reference.

Common mistakes & things to watch for

  • “Value must be greater than 0.” / “kVA must be greater than 0.”
  • “kW must be non-negative.”
  • “Voltage and current must be positive.” / “Voltage and kVA must be positive.”
  • Leaving a field blank doesn't show an error — it just won't show a result until enough fields are filled in.
Breaker Size CalculatorFree · Pro · Premium

Picks the correct standard breaker (or fuse) size for four different kinds of loads, following the rounding rules that apply to each.

How to use it

  1. Choose a Load Type: Branch Circuit, Feeder, Service, or Appliance.
  2. Choose whether you're entering the load in Amps or VA.
  3. Enter the continuous and non-continuous portions of the load, plus voltage and phase.
  4. Appliance load type has its own extra fields — see below.
  5. Read the recommended breaker size.

Input fields

  • Branch / Feeder / ServiceContinuous & non-continuous amps (or VA), voltage, phase; Service also asks for the disconnect type.
  • ApplianceAmps or VA, voltage, phase, and — if the nameplate lists one — its own maximum overcurrent protection rating.

What the result means

The recommended standard breaker size in Amps (rounded to a real, sellable size — e.g. 20, 30, 50 A), the math behind it, and any relevant warnings.

Common mistakes & things to watch for

  • If a nameplate lists its own maximum breaker size (MOCP), always use the Appliance fields for it — it overrides the general percentage-based calculation.
  • If the required amps exceed 6000 A, the calculator flags that it's outside the standard breaker size chart.
  • Air-conditioning and refrigerating equipment (NEC Article 440) moved to its own HVAC Calculator — it's no longer a load type here.
Load CalculationFree · Pro · Premium

Adds up all the electrical loads in a building — lighting, appliances, HVAC, motors, and more — and applies the code's demand-factor discounts to find the total service or feeder size you need.

How to use it

  1. Choose a Calculation Method that matches your project: Dwelling (Standard or Optional), Existing Dwelling, Multifamily (Optional), Commercial (Standard), Existing Building, New Restaurant, or Feeder/Service.
  2. Enter the square footage and voltage system.
  3. Fill in the loads that apply: small-appliance/laundry circuits, fixed appliances, ranges/dryers, heating/cooling, motors, receptacles, or (for existing buildings) your prior 12-month peak demand.
  4. Read the itemized breakdown and total.

Input fields

  • Square footage / voltage system120/240 1-phase, 120/208 3-phase, 277/480 3-phase, 240 3-phase, or 480 3-phase.
  • Small appliance / laundry circuitsMinimum of 2 and 1 respectively — these are code minimums, entering less doesn't go below them.
  • Fixed appliances, ranges, dryersEnter wattage/kW and count for each.
  • Heating and coolingOnly the larger of the two is counted — the calculator explains why the smaller one was excluded.
  • MotorsHorsepower, voltage, phase — the largest motor gets extra weight per code.
  • Receptacle count / VA eachDefaults to 180 VA per receptacle.
  • MultifamilyNumber of units and square footage per unit.
  • Existing BuildingExisting service size and a properly measured 12-month peak demand.

What the result means

A line-by-line list of each load category with its connected value and demand value (after code discount factors), a running total, the resulting amperage, and a recommended standard service/feeder size.

Common mistakes & things to watch for

  • Using the Multifamily method with fewer than 3 units triggers a note to use the standard dwelling method instead — the multifamily discount tables don't apply below 3 units.
  • The Existing Building method needs a real, properly measured 12-month peak demand reading — this shouldn't be estimated.
  • Sizing feeders/services for A/C or refrigerating equipment under Article 440 (RLA-based, largest unit at 125%) is done in the HVAC Calculator's Feeder/Service Load tab, not here — this calculator's Heating & Cooling fields are the general Article 220.60 noncoincident-load entry, not equipment-specific 440 sizing.
Motors CalculatorFree · Pro · Premium

Everything motor-related in one place: how much current a motor draws, what breaker it needs, and what wire size to run to it.

How to use it

  1. Pick a tab: Motor Load Calculation, Motor Breaker/OCPD, or Motor Wire Size.
  2. Choose the motor's horsepower from the dropdown — only standard values are listed, you can't type in a custom one.
  3. Choose voltage, phase, and motor type.
  4. Read the result for that tab.

Input fields

  • HorsepowerChosen from a fixed dropdown (1/6 HP up to 500 HP); single-phase motors are limited to 10 HP and below.
  • VoltageStandard values only (115, 200, 208, 230, 460, 575, 2300, depending on phase).
  • Phase / motor typeSingle or Three; e.g. AC squirrel-cage induction, synchronous.
  • Protection type (Breaker/OCPD tab)Inverse-time breaker, instantaneous-trip breaker, dual-element fuse, etc.
  • Wire Size tabSame wire-size fields as the Wire Size Calculator, plus single- or multiple-motor mode.

What the result means

Motor Load tab gives the full current draw in Amps and VA; Breaker/OCPD tab gives the recommended breaker/fuse size; Wire Size tab gives the minimum conductor size for that motor's circuit.

Common mistakes & things to watch for

  • If an exact horsepower/voltage combination isn't in the dropdown, it's because that combination isn't a standard one — pick the closest standard value or use the motor's actual nameplate current instead.
  • A motor's breaker size is intentionally different from — usually larger than — its wire size, because motor circuits are allowed a bigger breaker to handle starting current. That's expected, not a bug.
Transformer CalculatorFree · Pro · Premium

Everything transformer-related in one place: primary/secondary breaker sizing, secondary conductor tap rules, autotransformer OCPD sizing, a ground-fault protection requirement check, and load-sharing across paralleled transformer banks.

How to use it

  1. Pick a tab: OCPD Sizing, Secondary Conductor Taps, Autotransformer OCPD, Ground-Fault Protection, or Parallel Transformers.
  2. OCPD Sizing: enter the transformer's kVA rating, phase, primary voltage, secondary voltage, and whether it has secondary protection.
  3. Secondary Conductor Taps: enter the primary OCPD rating, primary/secondary voltages, the secondary conductor length, and the calculated secondary load.
  4. Autotransformer OCPD: enter the autotransformer's kVA rating, voltage, and phase.
  5. Ground-Fault Protection: pick the system grounding type, then enter the voltage to ground and the disconnect/OCPD rating.
  6. Parallel Transformers: add 2–4 units (kVA, %Z, secondary voltage, vector group each), pick the system phase, then enter either the total system load or one known unit's actual reading.
  7. Read the result for that tab.

Input fields

  • OCPD SizingkVA rating, phase, primary voltage, secondary voltage, and whether it has secondary protection.
  • Secondary Conductor TapsPrimary OCPD rating, primary voltage, secondary voltage, secondary conductor length (ft), and calculated secondary load (A).
  • Autotransformer OCPDkVA rating, voltage (≤600 V), and phase.
  • Ground-Fault ProtectionSystem grounding type (Solidly Grounded Wye, Corner-Grounded Delta, or Ungrounded/Other), voltage to ground, and disconnect/OCPD rating.
  • Parallel TransformersPer unit: kVA rating, %Z (nameplate), secondary voltage, and vector group (Δ-Δ, Y-Y, Δ-Y, or Y-Δ). Bank-wide: phase, and either the total system load (kVA or A) or one known unit's reading.

What the result means

OCPD Sizing gives primary (and secondary, if used) breaker min/max sizes plus disconnect sizing. Secondary Conductor Taps gives the applicable NEC 240.21(C) rule, the minimum secondary conductor ampacity, and whether a separate secondary OCPD is required. Autotransformer OCPD gives the maximum breaker/fuse rating. Ground-Fault Protection gives a Yes/No on whether GFPE is required, plus the maximum setting if it is. Parallel Transformers gives each unit's load share (using the inverse-%Z method), kVA/Amps drawn, and % loaded — flagging any unit that ends up over 100% even when the bank's combined capacity is sufficient.

Common mistakes & things to watch for

  • The Secondary Conductor Taps and Ground-Fault Protection tabs are threshold-screening design aids, not exhaustive implementations of NEC 240.21(C) or 450.5 — verify all applicability conditions and exceptions against the full NEC text before finalizing a design.
  • Autotransformer OCPD sizing (NEC 450.4) only applies to autotransformers 600 V or less that aren't part of an individual motor circuit, signal circuit, or Class 2 control circuit.
  • Parallel Transformers is an engineering-practice calculation (inverse-%Z load sharing), not a literal NEC rule — it will still compute a result for mismatched vector groups, secondary voltages, %Z spreads, or kVA ratios, but it flags them as warnings. Always verify against a manufacturer paralleling study or a licensed engineer before relying on it.
HVAC CalculatorFree · Pro · Premium

Everything air-conditioning and refrigerating equipment-related in one place per NEC Article 440: OCPD sizing, disconnect sizing, branch-circuit conductor sizing, multimotor/combination-load equipment, overload protection, room air conditioner rules, and building feeder/service load sizing.

How to use it

  1. Pick a tab: OCPD Sizing, Disconnecting Means, Branch-Circuit Conductor, Multimotor/Combo-Load, Overload Protection, Room Air Conditioners, or Feeder/Service Load.
  2. OCPD Sizing: enter the nameplate MCA and MOCP.
  3. Disconnecting Means: enter the nameplate RLA (or BCSC, whichever is greater).
  4. Branch-Circuit Conductor: enter the RLC/BCSC for a single motor-compressor.
  5. Multimotor/Combo-Load: enter each motor-compressor's RLC/BCSC (up to 4) plus the sum of other component loads (fans, resistance heat, etc.).
  6. Overload Protection: enter the RLC and pick a protection method (integral thermal protector, separate overload relay, or fuse/inverse-time breaker).
  7. Room Air Conditioners: enter the RLA, voltage, branch-circuit rating, and whether the unit shares its circuit with receptacles or other loads.
  8. Feeder/Service Load: add each HVAC unit's name, nameplate RLA, voltage, and phase — the largest unit is demanded at 125% (440.32) and the rest at 100% (440.33) — then read the total feeder/service demand.
  9. Read the result for that tab.

Input fields

  • OCPD SizingNameplate MCA (Minimum Circuit Ampacity) and MOCP (Maximum Overcurrent Protection).
  • Disconnecting MeansNameplate RLA (Rated-Load Current) or BCSC, whichever is greater.
  • Branch-Circuit ConductorRLC/BCSC for a single motor-compressor.
  • Multimotor/Combo-LoadRLC/BCSC of each motor-compressor (2-4 typical for dual-circuit rooftop units) plus other component loads.
  • Overload ProtectionNameplate RLC and the overload protection method in use.
  • Room Air ConditionersNameplate RLA and voltage (125 or 250 V), branch-circuit rating, and circuit type (individual, shared receptacles-only, or shared with lighting/other loads).
  • Feeder/Service LoadVoltage system, plus one row per HVAC unit with its name, nameplate RLA, voltage, and phase.

What the result means

OCPD Sizing gives the recommended breaker size. Disconnecting Means gives the minimum disconnect ampere rating. Branch-Circuit Conductor gives the minimum conductor ampacity. Multimotor/Combo-Load gives the combined minimum conductor ampacity and recommended OCPD size. Overload Protection gives the maximum overload setting (or confirms none is needed for factory-protected units). Room Air Conditioners gives a cord-and-plug permission check, minimum conductor/disconnect rating, and a shared-circuit de-rating check. Feeder/Service Load gives an itemized per-unit connected/demand VA breakdown, the totals, the calculated amperage, and a recommended standard feeder/service size.

Common mistakes & things to watch for

  • The Multimotor/Combo-Load, Overload Protection, Room Air Conditioner, and Feeder/Service Load tabs are screening design aids, not exhaustive implementations of NEC 440.22(B)/440.24, 440.52/440.53, 440.62, or 440.32/440.33 — always defer to equipment nameplate markings and verify exact subsection lettering against the adopted code edition.
  • This calculator used to be a load type inside the Breaker Size Calculator — it's now a standalone calculator with its own tabs.
  • The Feeder/Service Load tab needs at least one HVAC unit entered before it shows a result — with zero units it just shows the empty-state placeholder, not a warning.
PE Exam PreparationFree (limited) · Pro · Premium

Practice questions for the NCEES PE Power exam, with three modes depending on your plan.

How to use it

  1. Sign in — a free account is enough to track your daily questions.
  2. Pick a tab: Dashboard, Practice, or Timed Exam.
  3. Practice is open to everyone — Free accounts get 10 questions per day; Pro and Premium get unlimited practice.
  4. Dashboard (progress tracking) requires a Pro plan or higher.
  5. Timed Exam (full timed exams with a wrong-answers review) requires Premium.

Input fields

  • No calculation inputsAnswer multiple-choice, fill-in-the-blank, or drag-and-drop questions on screen.

What the result means

Immediate right/wrong feedback in Practice mode; a scored, timed session with a review of missed questions in Timed Exam mode; and, on Pro or higher, a running dashboard of your progress by topic.

Common mistakes & things to watch for

  • A “Plan Required” message on the Dashboard or Timed Exam tab is expected, not an error — those modes need a Pro plan (Dashboard) or a Premium plan (Timed Exam).
  • Free tier is limited to 10 practice questions per day.

FAQ

Using the Calculators

Subscriptions & Billing

Top